THETYS
The Thetys 60-160 kVA utilizes double online conversion architecture with inverter transformer, offers galvanic isolation between the continuous and alternate line guaranteeing excellent dynamic response performance. The IGBT rectifier with innovative sinewave input enables the reduction of input harmonics (THDi < %) and a power factor of the input ac near to unity (>0.99). This characteristics makes the Thetys highly compatable with the installation upstream of the UPS without having to install additional filters. The Thetys allows reduced costs for the most sophisticated data centres due to its compact dimensions and to its efficient design that enables an efficiency of over 94% to be achieved. It is possible to put the unit on the wall and side by side with other panels without losing performance due to a well designed cooling system. The UPS has a user-friendly interface with synoptic panel and LCD display and includes a wide range of connection options that simplifies the use and control in the installations. The Thetys is available in parallel configuration for redundancy and for power parallel. Installation is easy using parallel-ready technology that is included in the standard unit.
Available in 100-160 kVA.
AstridUPS All Rights Reserved.
Technical Specification
| UPS(Power-kVA) | 60 | 80 | 100 | 125 | 160 |
| Nominal input voltage-Vac | 400 + 10% -20%(380 – 415 adjustable) | ||||
| Nominal output voltage-Vac | 380÷415(adjustable) | ||||
| Nominal output power (PF 0,8)-kVA | 60 | 80 | 100 | 125 | 160 |
| Nominal output power (PF 1)- kW | 48 | 64 | 80 | 100 | 128 |
| Efficiency(AC+AC)-%- eco mode | >93 | ||||
| UPS ambient temperature -Celcius | 0 ÷40 | ||||
| Audible noise level (acc. EN 50091)dB | <60 | <60 | <60 | <60 | <60 |
| Immunity(EMI) | According “EN 50091-2″ (CE Label)” | ||||
| Battery test | automatic every month/manual | ||||
| Rectifier Bridge | IGBT – low harmonic distortion (<3%) | ||||
| Inverter Bridge | IGBT (high efficiency transformerless) | ||||
| Overload capability | 125% for 10′ -200% for 100ms | ||||
| Output harmonic distortion | <1% | ||||
| Output harmonic distortion non linear | <5% | ||||
| Crest factor(non linear load 75%) | 3:1 | ||||
| Dimensions LxPxH-mm | 815x820x1670 | ||||