Master MPS
Total Protection
Master MPS series UPS provide maximum protection and power quality for mission critical loads, including data centres, industrial processes, telecommunications, security and electro-medical systems. Master MPS is an on-line double conversion UPS (VFI SS 111- IEC EN 62040-3) with a transformer isolated inverter. The Master MPS range includes three-phase input and single-phase output versions from 10 to 100 kVA, and three-phase input and output versions from 10 to 800 kVA. All versions are provided with 6-pulse thrystor-based rectifier, with or without optional harmonic filters. A 12-pulse thrystor-based rectifier is available on request for the 60 and 80 kVA versions with or without optional harmonic filters.
Flexibility
Master MPS is suitable for a wide range of applications including IT and the most demanding industrial environments. The UPS is suitable for power capacitive loads such as blade servers, from 0.9 leading to 0,8 lagging with a broad range of accessories and options, complex configurations and system architectures can be achieved to guarantee maximum power availability and the option to add new UPS without interruption to existing installations.
For Datacentre, E-Medical, Industry, Transport, Emergency.
Available in 3:1 threephase/threephase 10-200kVA.
Available in 1:1 threephase/singlephase 10-100kVA
RielloUPS All Rights Reserved.
Technical Specification
| MODELS | MPM 10 BAT | MPM 15 BAT | MPM 20 BAT | MPM 30 | MPM 40 | MPM 60 | MPM 80 | MPM 100 |
| INPUT | ||||||||
| Nominal Voltage | 380-400-415 Vac three-phase | |||||||
| Voltage tolerance | 400 V +20% /- 25% | |||||||
| Frequency | 45-65 Hz | |||||||
| Soft start | 0-100% in 120″(selectable) | |||||||
| Permitted frequency tolerance | ± 2% (selectable from ±1% to ±5% from front panel) | |||||||
| Standard Equipment provided | Back feed protection; separable bypass line | |||||||
| BYPASS | ||||||||
| Nominal Voltage | 220-230-240 Vac single-phase + N | |||||||
| Nominal Frequency | 50 or 60 Hz (selectable) | |||||||
| OUTPUT | ||||||||
| Nominal power (kVA) | 10 | 15 | 20 | 30 | 40 | 60 | 80 | 100 |
| Active power (kW) | 9 | 13.5 | 18 | 27 | 36 | 54 | 72 | 90 |
| Number of phases | 1 | |||||||
| Nominal Voltage | 220-230-240 Vac single-phase + N(selectable) | |||||||
| Static stability | ±1% | |||||||
| Dynamic stability | ±5% in 10 ms | |||||||
| Voltage distortion | <1% with linear load/ <3% with non-linear load | |||||||
| Crest factor | 3:1 lpeack/lrms | |||||||
| Frequency stability on battery | 0.05% | |||||||
| Frequency | 50 or 60 Hz (selectable) | |||||||
| Overload | 110% for 60′; 125% for 10′:150% for 1′ | |||||||
| BATTERIES | ||||||||
| Type | VRLA AGM / GEL; NiCd; Supercaps; Li-ion;Flywheels | |||||||
| Residual ripple voltage | <1% | |||||||
| Temperature compensation | -0.5 V x °C | |||||||
| Typical charge current | 0.2 x c10 | |||||||
| INFO FOR INSTALLATION | ||||||||
| Weight without batteries(kg) | 200 | 220 | 230 | 270 | 302 | 440 | 500 | 580 |
| Dimensions (WxDxH)(mm) | 555x740x1400 | 800x740x1400 | 800x800x1900 | |||||
| Remote signals | dry contacts | |||||||
| Remote controls | ESD and bypass | |||||||
| Communications | Double RS232 + dry contacts + 2 slots for communication interface | |||||||
| Operating Temperature | 0°C/+40°C | |||||||
| Relative humidity | <95% non-condensing | |||||||
| Colour | Dark grey RAL 7016 | |||||||
| Noise level at 1m (ECO Mode) | 60 dBA | 62 dBA | ||||||
| IP Rating | IP20 | |||||||
| Smart Active efficiency | up to 98% | |||||||
| Standards | Directives LV 2006/95/EC-2004/108/EC;Safety IEC EN 62040-1;EMC IEC EN 62040-2;Performance IEC EN 62040-3 | |||||||
| Classification in accordance with IEC 62040-3 | (Voltage Frequency Independent) VFI -SS-111 | |||||||
| Moving the UPS | transpallet | |||||||